Partial discharges in free helium bubbles in transformer oil Full article

Conference ICHVE 2018 - 2018 IEEE International Conference on High Voltage Engineering and Application
10-13 Sep 2018 , Athens
Source 2018 IEEE International Conference on High Voltage Engineering and Application
Compilation, 2019.
Output data Year: 2019, Article number : 8642061, Pages count : DOI: 10.1109/ICHVE.2018.8642061
Authors Karpov D.I. 1 , Korobeynikov S.M. 2 , Ridel A.V. 2 , Ovsyannikov A.G. 2 , Meredova M.B. 1
Affiliations
1 Laventyev Institute of Hydrodynamics
2 Novosibirsk State Technical University

Abstract: Partial discharges (PD) in a floating bubble in transformer oil were studied experimentally and theoretically. In test cell, the PD inception was very rare event. Sometimes PD occurred after an exposition of more than 10 hours at the voltage that corresponds to the value three times larger than that required in accordance with the Paschen's law. The problem is in initiating electrons. Analysis showed that, at the conditions of PD occurrence in helium bubbles, the mechanism of breakdown corresponds to the streamer one. Registrations of electrical and optical signals of PD were performed to estimate both apparent charge and the number of radiated photons. As a result of estimation, number of electrons is approximately equal to the number of photons.
Cite: Karpov D.I. , Korobeynikov S.M. , Ridel A.V. , Ovsyannikov A.G. , Meredova M.B.
Partial discharges in free helium bubbles in transformer oil
In compilation 2018 IEEE International Conference on High Voltage Engineering and Application. 2019. DOI: 10.1109/ICHVE.2018.8642061 РИНЦ OpenAlex
Identifiers:
Elibrary: 38671323
OpenAlex: W2914174316
Citing:
DB Citing
OpenAlex 5
Altmetrics: